BTU & Cooling Load Calculator
From vendor documentationA live converter between watts, kilowatts, BTU/hr, tons of refrigeration and kcal/h, plus CRAC sizing: enter the rack load, see the heat rejection and the recommended unit size with a stated redundancy factor.
Live converter
Edit any field; the other four follow.
This is the field driving the conversion.
CRAC sizing
A stated factor, not a hidden fudge
Covers compressor cycling at part load, filter loading, and the equipment you will add later. 1.3 is a common planning figure.
Why a factor at all
Export
Conversion table and CRAC sizing
Cooling load
24.000 kW of IT load rejects the same amount of heat
- BTU/hr
- 81891.41
- Tons of refrigeration
- 6.824284
- Kilowatts
- 24
- kcal/h
- 20636.28
- Watts
- 24000
- Round-trip drift
- exact
× 3.412142
÷ 12,000 BTU/hr
Every watt drawn becomes heat.
× 0.859845
The canonical value every field is derived from.
W → BTU/hr → W. “exact” means the chain round-trips bit-for-bit.
CRAC / CRAH sizing
- Rack load in
- 24 kW
- Sizing factor
- × 1.3
- Required capacity
- 8.87 ton
- Recommended unit
- 9 ton
81891.41 BTU/hr
Stated so you can argue with it.
= 31.20 kW
≈ 31.65 kW. Catalogue sizes are discrete — check the model you are buying.
Worked conversion
Every step the numbers above went through
24 kW → 24000.000000 W 24000.000000 W × 3.412142 BTU/hr per W = 81891.4080 BTU/hr 81891.4080 BTU/hr ÷ 12000 BTU/hr per ton = 6.824284 ton 6.824284 ton × 3.516852 kW per ton = 24.000000 kW
One ton of refrigeration is 12 000 BTU/hr = 3.5169 kW
Definitions used
The constants behind every conversion
- BTU/hr per watt
- 3.412142
- BTU/hr per ton
- 12,000
- Watts per ton
- 3516.8525
- kW per ton
- 3.516852
- kcal/h per watt
- 0.859845
- Conversion basis
- BTU/hr
1 W = 3.412142 BTU/hr.
Exact, by definition of the refrigeration ton.
12000 ÷ 3.412142. Quoted as 3516.853 W in vendor literature.
Quoted as 3.516853 kW.
1 W = 3.6 kJ/h and 1 kcal = 4.1868 kJ.
BTU/hr is the pivot, so the two definitional conversions are exact.
Frequently asked
- How many BTU per hour is one watt?
- 1 W = 3.412142 BTU/hr. A 10 kW rack therefore rejects 34 121 BTU/hr of heat, and every watt drawn by IT equipment becomes heat inside the room.
- How many kW is a ton of refrigeration?
- A ton of refrigeration is 12 000 BTU/hr, which is 3.5169 kW (3.516851 kW from 12 000 ÷ 3.412142). Cooling units are sold in tons in North America and in kW almost everywhere else.
- Why size the CRAC above the calculated load?
- The calculated figure is the steady-state heat rejection. A sizing factor covers compressor cycling, part-load efficiency, filter loading, and the fact that you will add equipment. The tool states the factor it applied so you can change it.
- Does a UPS or PDU add to the cooling load?
- Yes, but far less than the IT load. Losses in the electrical path — typically 2–6 % of throughput — also end up as heat in the room, so add them if the room is close to its limit.
Next
- PDU Power & Breaker CalculatorTurn a rack load in watts into line current for single- or three-phase feeds, apply the 80 % continuous derating, pick the next standard breaker size and count the C13 and C19 receptacles the load needs.
- Cabling Pinout & Fibre Polarity ReferenceT568A and T568B side by side as tables and as colour-coded strip diagrams, plus crossover and Cisco rollover wiring, PoE Mode A/B pin usage with the 802.3af/at/bt classes, MPO/MTP polarity A/B/C and the copper and fibre Ethernet standards.